The user is responsible for all changes and repairs made to the device by the user or the user’s agent. • All new components are to be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only.
SITRANS WM100 Motion Sensing Switch SITRANS WM100 motion sensing switch is a heavy-duty zero speed alarm. It is used to detect the absence or presence of motion of rotating, reciprocating, or conveying equipment. The WM100 has a circuit card and a magnetic assembly potted in the probe body.
The Manual Notes: • The SITRANS WM100 product is to be used only in the manner outlined in this instruction manual. • This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications.
• minimum 6 or 12 pulses per minute • maximum 3000 pulses per minute Shipping Weight • 2 kg (4.4 lbs) Approvals • CSA , CE, C-TICK US/C Selected via a common jumper. Refer to Operation. 7ML19985MW01 SITRANS WM100 – OPERATING INSTRUCTIONS Page 3...
20 mm to over 100 mm from the face of the target to the face of the probe. The range is dependent on the target type and range of speed expected. See typical performance graphs on page 9 for examples. Page 4 SITRANS WM100 – OPERATING INSTRUCTIONS 7ML19985MW01...
Connection of the probe should be made via flexible conduit for easier removal or adjustment of the probe. In climates where direct sunlight may cause the SITRANS WM100 Note: temperature to rise above the specified limit, shade the unit by installing a sun shield.
For 5 second time delay and minimum 12 ppm range, connect jumper across terminals 7 and 8. Without a jumper, the default is 10 second time delay and minimum 6 ppm range. Page 6 SITRANS WM100 – OPERATING INSTRUCTIONS 7ML19985MW01...
WM100 contact to latch. In such a case, program a timer contact into circuit. CSA requires a 3 A or less fuse to protect contacts. For 240 V AC, protect contacts with a 1500 VA transformer as well. 7ML19985MW01 SITRANS WM100 – OPERATING INSTRUCTIONS Page 7...
Note that detection range may vary slightly with voltage supply and temperature, so it is recommended to use the minimum air gap that is physically safe to implement. Page 8 SITRANS WM100 – OPERATING INSTRUCTIONS 7ML19985MW01...
Setup E: DC motor DC motor with 5/8" drive shaft 3/16" sq. key and 3/16" square 5/8" shaft WM100 1000 10000 Note: 1 m/s ~ 200 ft/min; 25 mm ~ 1.0" 7ML19985MW01 SITRANS WM100 – OPERATING INSTRUCTIONS Page 9...
114 mm (4.5") BCD, 4 places Maintenance The WM100 can be cleaned by wiping the enclosure exterior with a damp cloth. No further maintenance is required for the device. Page 10 SITRANS WM100 – OPERATING INSTRUCTIONS 7ML19985MW01...