Communication
11.10 DR 7 Process interfaces
NOTICE
Risk to the plant
If an output is set following a fault (operating error), this can pose a risk for the plant.
Ensure that the parameters are correctly set.
11.10.6
Analog output range
This parameter is used to define the output current range.
Value
0
1
11.10.7
Analog output source
The analog output can be used for a range of purposes. This parameter defines the tag that
controls the analog output.
Value
0
1
2
3
4
11.10.8
Response of analog output to faults or SIMATIC STOP
This parameter defines the response of the analog output following a fault of the SIWAREX
module or SIMATIC STOP.
Value
0
1
2
3
130
Response
Switch off
Retain function
Output configured output value, e.g. 3.5 mA
Output maximum value (24 mA, NAMUR)
Output current
0 ... 20 mA
4 ... 20 mA
Basis for the analog output
Belt speed
Belt load
Material flow rate
External specification, DR 17
(Specified in mA)
Via SIMATIC S7 interface