Table 18-1 Conversion Number Table - Omega DP41-B User Manual

Universal input meter
Hide thumbs Also See for DP41-B:
Table of Contents

Advertisement

18
Multi-Point Scale and Offset Menu Configuration
Determine the correct values for Inputs ("INPUt 0" and "INPUt 1"). Calculate "INPUt 0" and "INPUt 1"
using the following equation:
Conversion number is a coefficient of conversion between input values and real full display
range (100000 counts). See table below for proper conversion number.
Determine "INPUt 0" and "INPUt 1" Input range. For our transducer select 0 – 100 mV range.
1.
Determine correct values for Display Reading ("REAd 0" and "REAd 1")
2.
In most cases,"REAd 0" and "REAd 1" are equal to the minimum and the maximum of the
transducer output range.
3. Scaling the controller.
Press 'RESET/ENTER'
Press 'RESET/ENTER'
Press 'RESET/ENTER'
Press ' /MAX' & '
Press 'RESET/ENTER'
Press 'RESET/ENTER'
Press ' /MAX' & '
Press 'RESET/ENTER'
Press 'RESET/ENTER'
Press ' /MAX' & '
Press 'RESET/ENTER'
Press 'RESET/ENTER'
Press ' /MAX' & '
Press 'RESET/ENTER'
68
"INPUt" = (Sensor Output) x (Conversion Number)
INPUT RANGE
0 – 100 mV
0 - 1 V
0 - 10 V
0 – 20 mA
Table 18-1. Conversion Number Table
"INPUt 0" = 0 (mV) x 1000(cts/mV) = 000000
"INPUt 1" = 30 (mV) x 1000(cts/mV) = 030000
"REAd 0" = 000000
"REAd 1" = 000100
18) Display stops flashing "MANUAL" Manual Scaling method menu.
19) Display shows "StOREd" momentarily and advances to "INPUt 0"
heading.
20) Display shows last stored "INPUt 0" value with 1st digit flashing.
/MIN'
21) To enter "INPUt 0" value (000000)
22) Display advances to "REAd 0" heading.
23) Display shows last stored "REAd 0" value with 1st digit flashing.
/MIN'
24) To enter "REAd 0" value (000000).
25) Display shows "INPUt 1" heading.
26) Display shows last stored "INPUt 1" value with 1st digit flashing.
/MIN'
27) To enter "INPUt 1" value (030000).
28) Display advances to "REAd 1" heading.
29) Display shows last stored "REAd 1" value with 1st digit flashing.
/MIN'
30) To enter "REAd 0" value (000100).
31) Display shows "StOREd" momentarily and advances to "OUt.CNF"
Output Configuration Menu.
CONVERSION NUMBER
100000/(100 x 1)=1000cts/mV
100000/(1000 x 1)= 100cts/V
100000/(1000 x 10)= 10cts/V
20000/ (20 x 1) = 1000cts/mA