Safety Considerations - Omega DP41-B User Manual

Universal input meter
Hide thumbs Also See for DP41-B:
Table of Contents

Advertisement

3

Safety Considerations

3.1 SAFETY CONSIDERATIONS
This device is marked with the international caution symbol. It is important to read this
manual before installing or commissioning this device as it contains important
information relating to Safety and EMC (Electromagnetic Compatibility).
Unpacking & Inspection
Unpack the instrument and inspect for obvious shipping damage. Do not attempt to
operate the unit if damage is found.
This instrument is a panel mount device protected in accordance with EN 61010:2001,
electrical safety requirments for electrical equipment for measurement , control and
laboratory. Installation of this instrument should be done by Qualified personnel. In
order to ensure safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-breaker shall be included in the
building installation as a disconnecting device. It shall be marked to indicate this function, and it shall
be in close proximity to the equipment within easy reach of the operator. The switch or circuit-breaker
shall not interrupt the Protective Conductor (Earth wire), and it shall meet the relevant requirements of
IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). The switch shall not be
incorporated in the mains supply cord.
Furthermore, to provide protection against excessive energy being drawn from the mains supply in
case of a fault in the equipment, an overcurrent protection device shall be installed.
• The Protective Conductor must be connected for safety reasons.
Check that the power cable has the proper Earth wire, and it is properly
connected. It is not safe to operate this unit without the Protective Conductor
Terminal connected.
• Do not exceed voltage rating on the label located on the top of the instrument
housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure instrument does not
exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to minimize
electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems
persist.
6

Advertisement

Table of Contents
loading

Table of Contents