6.1 THERMOCOUPLE Input:

S1_G/J; S2_A/B/K, jumpers are closed as shown:
S1

6.2 RTD Input:

6.2.1 For RTDs:

S1_H; S2_A/B/F/J, jumpers are closed as shown:
S1
S2

6.2.2 For RTD 10 ohm copper:

S1_H; S2_A/B/F/J/L, jumpers are closed as shown:
S1

6.3 VOLTAGE/PROCESS VALUE Input:

6.3.1 For ± 50mV, 0-100mV ranges:
S1_K; S2_A/B/G/H, jumpers are closed as shown:
NOTE: For some applications, the internal excitation is required; install jumpers G and H on S2 (as
factory preset). If the external excitation is used, then remove jumper G only. These configurations are
also applied to other Voltage/Process Input ranges.
S1
6.3.2 For ± 500mV, 0-1V ranges:
S1_K/E/F; S2_G/H, jumpers are closed as shown:
6.3.3 For ± 5V, 0-10V ranges:
S1_K/C/D; S2_G/H, jumpers are closed as shown:
S1
S1

Jumper Positions

S2
S2
S2
S2
S2