The alarm is deleted again if the current measured value (channel 2) falls below 29 °C.
Measured value (channel 1) = 21 °C
Measured value (channel 2) = 21 °C, tolerance band comparison is active.
Negative tolerance = -10 °C
Negative hysteresis = 2 °C
The alarm is generated if the current measured value (channel 2) is below 11 °C.
The alarm is deleted again if the current measured value (channel 2) rises above 13 °C.
NOTE!
In the example shown, channel 1 is constant and channel 2 changes its measured value. This
does not have to be the case. It can also be the case that channel 1 changes or even that
both channels change.
13.11.2 Digital channels
Setup dialog
Parameter
Parameter
Input signal
Selection/settings
6 channels can be assigned to each of the 9 groups.
Digital input x
Digital selector
13 Configuration
Description
Assigned signal
Signal that is to be allocated to the input.
155