Real-Time Clock
Function File

Real-Time Clock Function File

Feature
YR - RTC Year
MON - RTC Month
DAY - RTC Day of Month
HR - RTC Hours
MIN - RTC Minutes
SEC - RTC Seconds
DOW - RTC Day of Week
DS - Disabled
BL - RTC Battery Low
The real-time clock provides year, month, day of month, day of week,
hour, minute, and second information to the Real-Time Clock (RTC)
Function File in the controller.
The Real-Time Clock parameters and their valid ranges are shown in the
table below.
Address
Data Format
RTC:0.YR
word
RTC:0.MON
word
RTC:0.DAY
word
RTC:0.HR
word
RTC:0.MIN
word
RTC:0.SEC
word
RTC:0.DOW
word
RTC:0/DS
binary
RTC:0/BL
binary
Writing Data to the Real-Time Clock
The programming screen is shown below:
When valid data is sent to the real-time clock from the programming
device or another controller, the new values take effect immediately. In
RSLogix 500/RSLogix Micro, click on Set Date & Time in the RTC Function
File screen to set the RTC time to the current time on your PC.
Range
Type
1998...2097
status
1...12
status
1...31
status
0...23 (military time)
status
0...59
status
0...59
status
0...6 (Sunday to Saturday)
status
0 or 1
status
0 or 1
status