16
I/O Configuration
Embedded I/O
Catalog
Description
Number
Input
Power
1766-L32BWA
100/240V AC
1766-L32AWA
1766-L32BXB
24V DC
1766-L32BWAA 100/240V AC
1766-L32AWAA
1766-L32BXBA
24V DC
(1) Isolated RS-232/RS-485 combo port. Same as ML1100 Comm 0
(2) Non-isolated RS-232. Standard D-sub connector
Publication 1766-RM001A-EN-P - October 2008
The MicroLogix 1400 provide discrete I/O and analog input that is built
into the controller as listed in the following table. These I/O points are
referred to as Embedded I/O.
User
Embedded
Power
Discrete I/O
24V DC
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
12 Relay Outputs
None
20 120V AC Inputs
12 Relay Outputs
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
6 Relay Outputs
3 Fast DC Outputs
3 Normal DC Outputs
24V DC
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
12 Relay Outputs
None
20 120V AC Inputs
12 Relay Outputs
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
6 Relay Outputs
3 Fast DC Outputs
3 Normal DC Outputs
AC embedded inputs have fixed input filters. DC embedded inputs have
configurable input filters for a number of special functions that can be
used in your application. These are: high-speed counting, event input
interrupts, and latching inputs. The 1766-L32BXB and 1766-L32BXBA have
three high-speed outputs for use as pulse train output (PTO) and/or pulse
width modulation (PWM) outputs.
Embedded
Comm.
Analog I/O
Ports
None
1 RS232/RS485
1 Ethernet
(2)
1 RS232
4 Voltage Inputs
2 Voltage Outputs
(1)

Hide quick links: