Allen-Bradley MicroLogix 1400 Instruction Manual page 500

Programmable controllers
Hide thumbs Also See for MicroLogix 1400:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
498
Socket Interface Using CIP Generic Messaging
Publication 1766-RM001A-EN-P - October 2008
MSG Configuration Parameters
To call this service, click "Setup Screen" in the MSG instruction and enter
the values displayed below.
Configure the MSG with these values:
CIP Generic Msg Parameter
Channel
Communication Command
Service
Service Code
Class
Instance
Attribute
Data Table Address (Send)
Size in Bytes (Send)
Data Table Address (Receive)
Size in Bytes (Receive)
Description
1 (Integral)
CIP Generic
Custom
50 (hexadecimal)
342 (hexadecimal)
0 Use a relay ladder instruction to move the returned
instance number from a CreateSocket service into the
MGx:y.TFN element of a MSG instruction.
0
Specify N file
4 bytes
Specify N file.
12 bytes