Allen-Bradley MicroLogix 1400 Instruction Manual page 25

Programmable controllers
Hide thumbs Also See for MicroLogix 1400:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
Specialty I/O Configuration
1762-IR4 RTD/Resistance Module Input Data File
For each module, slot x, words 0...3 contain the analog values of the
inputs. Words 4 and 5 provide sensor/channel status feedback. The input
data file for each configuration is shown below.
Table: 0.A
Wor
15
14
d/Bit
0
Analog Input Data Channel 0
1
Analog Input Data Channel 1
2
Analog Input Data Channel 2
3
Analog Input Data Channel 3
4
Reserved
5
U0 O0 U1 O1
The bits are defined as follows:
• Sx = General status bits for input channels 0...3. These bits are set
(1) when an error (over- or under-range, open-circuit or input data
not valid condition) exists for that channel, or there is a general
module hardware error. An input data not valid condition is
determined by the user program. See MicroLogix 1200 RTD/
Resistance Input Module User Manual, publication 1762-UM003, for
details.
• OCx = Open-circuit indication for channels 0...3, using either RTD
or resistance inputs. Short-circuit detection for RTD inputs only.
Short-circuit detection for resistance inputs is not indicated because
0 is a valid number.
• Ox = Over-range flag bits for input channels 0...3, using either RTD
or resistance inputs. These bits can be used in the control program
for error detection.
• Ux = Under-range flag bits for channels 0...3, using RTD inputs
only.
These bits can be used in the control program for error detection.
Under-range detection for direct resistance inputs is not indicated
because 0 is a valid number.
13
12
11
10
9
8
OC
OC
OC
OC
3
2
1
0
U2
O2
U3
O3
I/O Configuration
7
6
5
4
3
2
Reserved
S3
S2
Reserved
Publication 1766-RM001A-EN-P - October 2008
25
1
0
S1
S0