Allen-Bradley MicroLogix 1400 Instruction Manual page 559

Programmable controllers
Hide thumbs Also See for MicroLogix 1400:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
The mode of the controller after the transfer takes place is determined by
the controller mode switch and the Power-Up Mode Behavior Selection
bit (S:1/12).
See also:LE - Load on Error on page 62.
Load Memory Module Always
Address
Data Format
S:1/11
binary
For this option to work, you must set (1) this bit in the control program
before downloading the program to a memory module. When this bit is
set in the memory module and power is applied, the controller
downloads the memory module program.
The mode of the controller after the transfer takes place is determined by
the controller mode switch and the Power-Up Mode Behavior Selection
bit (S:1/12).
See also:LA - Load Always on page 62.
Power-Up Mode Behavior
Address
Data Format
S:1/12
binary
If Power-Up Mode Behavior is clear (0 = Last State), the mode at
power-up is dependent upon the:
• position of the mode switch
• state of the Major Error Halted flag (S:1/13)
• mode at the previous power down
If Power Up Mode Behavior is set (1 = Run), the mode at power-up is
dependent upon the:
• position of the mode switch
• state of the Major Error Halted flag (S:1/13)
IMPORTANT
Range
Type
0 or 1
control
Range
Type
0 or 1
control
If you want the controller to power-up and enter the Run mode, regardless
of any previous fault conditions, you must also set the Fault Override bit
(S:1/8) so that the Major Error Halted flag is cleared before determining the
power up mode.
System Status File
User Program Access
read only
User Program Access
read only
Publication 1766-RM001A-EN-P - October 2008
557