Recipe and Data Logging
Publication 1766-RM001A-EN-P - October 2008
Number of Records
Using Queue 0 as an example, each record consumes:
Record Field
Memory Consumption
Date
2 bytes
Time
2 bytes
N7:11
2 bytes
L14:0
4 bytes
T4:5.ACC
2 bytes
I1:3.0
2 bytes
B3:2
2 bytes
Integrity Check
2 bytes
Total
18 bytes
In this example, each record consumes 18 bytes. So if one queue was
configured, the maximum number of records that could be stored would
be 7281. The maximum number of records is calculated by:
Maximum Number of Records = Data Log File Size/Record Size
Example Queue 5
Queue 5 (Time =
, Delimiter = TAB)
Time
Record 0
20:00:00
Record 1
20:30:00
Record 2
21:00:00
Record 3
21:30:00
Record 4
22:00:00
Record 5
22:30:00
Record 6
23:00:00
String Length of Record
The size of a record is limited so that the length of the maximum
formatted string does not exceed 109 characters. The following table can
be used to determine the formatted string length.
= 128K bytes/18 bytes
= (128)(1024)/18
= 7281 records
N7:11
TAB
2315
TAB
8190
TAB
2400
TAB
8210
TAB
2275
TAB
8150
TAB
2380
TAB
8195
TAB
2293
TAB
8390
TAB
2301
TAB
8400
TAB
2308
TAB
8100
I1:3.0
I1:2.1
TAB
4465
TAB
4375
TAB
4335
TAB
4360
TAB
4375
TAB
4405
TAB
4395

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents