Types of Interrupts Disabled by the UIF Instruction
Interrupt
EII - Event Input Interrupt
HSC - High-Speed Counter
EII - Event Input Interrupt
HSC - High-Speed Counter
EII - Event Input Interrupt
HSC - High-Speed Counter
EII - Event Input Interrupt
HSC - High-Speed Counter
EII - Event Input Interrupt
EII - Event Input Interrupt
HSC - High-Speed Counter
EII - Event Input Interrupt
EII - Event Input Interrupt
HSC - High-Speed Counter
STI - Selectable Timed Interrupt
Note: Bit 15 must be set to zero
To flush interrupt(s):
1. Select which interrupts you want to flush.
2. Find the Decimal Value for the interrupt(s) you selected.
3. Add the Decimal Values if you selected more than one type of
interrupt.
4. Enter the sum into the UIF instruction.
For example, to disable EII Event 1 and EII Event 3:
EII Event 1 = 32, EII Event 3 = 4
32 + 4 = 36 (enter this value)
Using Interrupts
Element
Decimal
Value
Event 4
16384
HSC2
8192
Event 5
4096
HSC3
2048
Event 6
1024
HSC4
512
Event 7
256
HSC5
128
Event 0
64
Event 1
32
HSC0
16
Event 2
8
Event 3
4
HSC1
2
STI
1
Publication 1766-RM001A-EN-P - October 2008
317
Corresponding
Bit
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0