IIM - Immediate Input
with Mask
IIM
IIM
Immediate Input w/Mask
Slot
I:0.0
Mask
N7:0
Length
1
303
Input and Output Instructions
The input and output instructions allow you to selectively update data
without waiting for the input and output scans.
Instruction
IIM - Immediate Input with Mask Update data prior to the normal input scan.
IOM - Immediate Output with
Mask
REF - I/O Refresh
Instruction Type: output
This instruction is used for embedded I/O only. It is not designed to be used
TIP
with expansion I/O.
Execution Time for the IIM Instruction
Controller
MicroLogix 1400
Used To:
Update outputs prior to the normal output scan.
Interrupt the program scan to execute the
I/O scan (write outputs, service
communications, read inputs)
When Rung Is:
True
False
10.9098 µs
0.2064 µs
Publication 1766-RM001A-EN-P - October 2008