Allen-Bradley MicroLogix 1400 Instruction Manual page 251

Programmable controllers
Hide thumbs Also See for MicroLogix 1400:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
Clearing S:14 before executing the FRD instruction is shown below:
I:1
] [
0
When the input condition I:0/1 is set (1), a BCD value (transferred from a
4-digit thumbwheel switch for example) is moved from word N7:2 into
the math register. Status word S:14 is then cleared to make certain that
unwanted data is not present when the FRD instruction is executed.
MOV
MOVE
Source
N7:2
4660
Dest
S:13
4660
CLR
CLEAR
Dest
S:14
0
FRD
FROM BCD
Source
S:13
00001234
Dest
N7:0
1234
Publication 1766-RM001A-EN-P - October 2008
Conversion Instructions
249
0001 0010 0011 0100
S:13 and S:14 are
displayed in BCD format.
0000 0100 1101 0010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents