Using High-Speed Outputs
Element Description
OF - PWM Output Frequency
Publication 1766-RM001A-EN-P - October 2008
PWMX Enable Hard Stop (EH)
Element Description
EH - PWM Enable Hard Stop
The PWMX EH (Enable Hard Stop) bit stops the PWM sub-system
immediately. A PWM hard stop generates a PWM sub-system error.
• Set (1) - Instructs the PWM sub-system to stop its output modulation
immediately (output off = 0).
• Cleared (0) - Normal operation.
PWMX Enable Status (ES)
Element Description
Address
ES - PWM Enable Status PWMX:0/ES bit
The PWMX ES (Enable Status) is controlled by the PWM sub-system.
When the rung preceding the PWM instruction is solved true, the PWM
instruction is enabled, and the enable status bit is set. When the rung
preceding the PWM instruction transitions to a false state, the enable
status bit is reset (0) immediately.
• Set (1) - PWM is enabled.
• Cleared (0) - PWM has completed or the rung preceding the PWM is
false.
PWMX Output Frequency (OF)
Address
Data Format
PWMX:0.OF long word
(32-bit INT)
The PWMX OF (Output Frequency) variable defines the frequency of the
PWM function. This frequency can be changed at any time. In the
MicroLogix 1400 controller, the data less than zero or greater than 40,000
generates a PWM error.
Address
Data
Range Type
Format
PWMX:0/EH bit
0 or 1
Data Format
Range Type
0 or 1
Range
Type
0...40,000
control read/write
User Program
Access
control read/write
User Program
Access
status
read only
User Program Access