Setting guidelines

Scheme communication and tripping for faults occurring during power
swinging over the protected line
The IED includes generally up to five distance protection zones. It is possible to use
one or two of them intentionally for selective fault clearing during power swings only.
Following are the basic conditions for the operation of the so called (underreaching and
overreaching) power-swing zones:
Measured
impedance at initital
fault position
Impedance locus at initial power
swing after the fault clearance