ABB RELION RET670 Applications Manual page 447

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
Transformer protection RET670 2.2 ANSI
Application manual
X
=
X
+
X
0E
0
m0
EQUATION554 V1 EN-US
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
Z
0
m
= -
K
0 1
×
+
+
2
Z
1
Z
0
R
f
EQUATION1426 V1 EN-US
If the denominator in equation
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
×
X m
0
Re
( )
= -
Re
K
0
1
( )
2
+
Re
B
Im
EQUATION1427 V2 EN-US
( )
×
( )
X m
0
Im
=
Im
K
0
( )
2
+
Re
B
Im
EQUATION1428 V2 EN-US
Parallel line is out of service and grounded in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
2
æ
X
m0
×
ç
R
=
R
1
+
------------------------- -
0E
0
2
è
R
+
X
0
0
EQUATION561 V1 EN-US
2
æ
X
m0
×
X
=
X
ç
1
------------------------- -
0E
0
2
2
è
R
+
X
0
0
EQUATION562 V1 EN-US
354
is called B and Z0m is simplified to X0m, then the
B
( )
2
B
B
( )
2
B
ö
÷
2
ø
ö
÷
ø
Section 8
Impedance protection
(Equation 353)
(Equation 354)
(Equation 355)
(Equation 356)
GUID-EC052207-C9AF-47EC-999A-BD485378FD9E v1
(Equation 357)
(Equation 358)
441