ABB RELION RET670 Applications Manual page 279

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
Transformer protection RET670 2.2 ANSI
Application manual
ANSI05000224 V2 EN-US
Figure 131:
Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
infeed from remote end"
infeed. For example, for faults between the T point and B station the measured
impedance at A and C will be
I
+ I
A
C
Z
=Z
+
A
AT
I
A
DOCUMENT11524-IMG3509 V3 EN-US
+
I
I
A
=
+
+
Z
Z
(Z
C
Trf
CT
I
C
EQUATION1714 V1 EN-US
A
, that is increased measured impedance due to fault current
·Z
TF
V2
C
×
×
2
Z ) (
)
TB
V1
Impedance protection
B
C
ANSI05000224-2-en.vsd
Section 8
M17048-245 v4
BC
"Fault
(Equation 132)
(Equation 133)