Table 70:
General settings parameters for the Measurement function
Setting
Short description
Operation
Operation Off/On
PowAmpFact
Amplitude factor to scale power
calculations
PowAngComp
Angle compensation for phase
shift between measured I & V
Mode
Selection of measured current
and voltage
k
Low pass filter coefficient for
power measurement, V and I
VGenZeroDb
Zero point clamping in % of
Vbase
IGenZeroDb
Zero point clamping in % of
Ibase
VBase (set in
Base setting for voltage level in
Global base)
kV
IBase (set in
Base setting for current level in
Global base)
A

Gas medium supervision SSIMG (63)

Identification
Function description
Insulation gas monitoring function
Application
Gas medium supervision (SSIMG ,63) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the
circuit breaker operation shall be blocked to minimize the risk of internal failure.
Binary information based on the gas pressure in the circuit breaker is used as an input
signal to the function. The function generates alarms based on the received
information.
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
0.0
Typically no angle compensation is
required. As well here required
direction of P & Q measurement is
towards protected object (as per IED
internal default direction)
Arone
Generator VTs are connected
between phases (V-connected)
0.00
Typically no additional filtering is
required
25%
Set minimum voltage level to 25%
3
Set minimum current level to 3%
15,65
Set generator rated phase-to-phase
voltage
3690
Set generator rated current
IEC 61850
IEC 60617
identification
identification
SSIMG
-
Transformer protection RET670 2.2 ANSI
1MRK 504 163-UUS A
On
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3