Blocking Of The Function Block - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
17.1.2.6
17.1.3
17.2
Transformer protection RET670 2.2 ANSI
Application manual
The trip function (SMPPTRC) splits up the directional data as general output data for
BFI_3P, BFI_A, BFI_B, BFI_C, STN, FW and REV.
All start and directional outputs are mapped to the logical node data model of the trip
function and provided via the IEC 61850 attributes dirGeneral, DIRL1, DIRL2, DIRL3
and DIRN.

Blocking of the function block

Total block of the trip function is done by activating the input BLOCK and can be used
to disable the outputs of the trip logic in the event of internal failures. Block of lock-
out output is achieved by activating the input BLKLKOUT.
Setting guidelines
The parameters for tripping logic SMPPTRC (94) are set via the local HMI or
PCM600.
Operation: Sets the mode of operation. Disabled switches the tripping off. The normal
selection is Enabled.
Program: Sets the required tripping scheme. Normally 3 phase or 1p/3p is used.
TripLockout: Sets the scheme for lock-out. Disabled only activates the closing circuit
lock-out output. Enabled activates the closing circuit lock-out output and latches the
TRIP related outputs. The normal selection is Disabled.
AutoLock: Sets the scheme for lock-out. Disabled only activates lock-out through the
input SETLKOUT. Enabled additionally allows lock-out activation via the trip inputs.
The normal selection is Disabled.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set to
ensure that the circuit breaker is opened correctly. The normal setting is 0.150s.
tWaitForPHS: Sets a duration after any of the inputs 1PTRZ or 1PTRGF has been
activated during which external pole selection must operate in order to get a single pole
trip. If no pole selection has been achieved, a three-pole trip will be issued after this
time has elapsed.
tEvolvingFault: Secures two- or three-pole tripping depending on Program selection
during evolving faults.
Trip matrix logic TMAGAPC
Section 17
Logic
M14828-21 v4
M12274-3 v8
IP15121-1 v4
845

Hide quick links:

Advertisement

Table of Contents
loading