Fault Infeed From Remote End - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

Section 8
Impedance protection
8.1.2.3
192
way as for solid grounded networks, distance protection has limited possibilities to
detect high resistance faults and must, therefore, always be complemented with other
protection function(s) that can carry out the fault clearance in this case.

Fault infeed from remote end

All transmission and most all sub transmission networks are operated meshed. Typical
for this type of network is that we will have fault infeed from remote end when fault
occurs on the protected line. The fault infeed may enlarge the fault impedance seen by
the distance protection. This effect is very important to keep in mind when both
planning the protection system and making the settings.
With reference to figure 69, we can draw the equation for the bus voltage Va at left side
as:
=
× ×
+
+
V
I p Z
(
I
A
A
L
A
EQUATION1273 V1 EN-US
If we divide Va by IA we get Z present to the IED at A side
V
I
=
=
×
+
Z
a
p Z
A
A
L
I
A
EQUATION1274 V2 EN-US
The infeed factor (IA+IB)/IA can be very high, 10-20 depending on the differences in
source impedances at local and remote end.
V
A
Es
A
A
Z
SA
ANSI05000217 V1 EN-US
Figure 69:
Influence of fault infeed from remote end
The effect of fault current infeed from remote end is one of the most driving factors to
justify complementary protection to distance protection.
×
I
)
R
B
f
+
I
×
B
R
f
I
A
p*ZL
(1-p)*ZL
I
A
ZL
21
R
f
1MRK 504 163-UUS A
(Equation 33)
(Equation 34)
VA
Es
B
I
Z
B
SB
21
en05000217_ansi.vsd
Transformer protection RET670 2.2 ANSI
Application manual
SEMOD168232-84 v2
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents