ABB RELION RET670 Applications Manual page 909

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
Transformer protection RET670 2.2 ANSI
Application manual
140°C
130°C
120°C
110°C
100°C
90°C
80°C
10
12
2
4
6
8
12
Hours of the day
Normal life expectancy loading
140°C
130°C
120°C
110°C
100°C
90°C
80°C
10
12
2
4
6
8
12
Hours of the day
Long time energy loading
IEC15000441 V1 EN-US
Figure 412:
Typical load cycles for example
Impact of the increased currents and temperature leads to premature transformer failure
and this may have an immediate short term effect or a cumulative long term effect.
Short-term effect: Reduction in dielectric strength due to the possible presence of
gas bubbles which leads to super saturation of the oil and reduction in short circuit
strength.
Long-term effect: Continuous deterioration of the conductor reduces the
transformer life.
Deterioration of insulation reduces mechanical strength and dielectric strength. Heating
from heavy overload or large electromagnetic force resulting from short circuit causes
expansion and unusual movement of conductors and it leads to turn-to-turn fault.
140°C
130°C
120°C
110°C
100°C
90°C
80°C
2
4
6
8
10
12
2
170°C
160°C
150°C
140°C
130°C
120°C
110°C
100°C
90°C
2
4
6
8
10
12
2
Section 18
Monitoring
10
4
6
8
12
2
4
6
Hours of the day
Planned loading beyond nameplate rating
10
4
6
8
12
2
4
6
Hours of the day
Short time energy loading
IEC15000441-1-en.vsdx
8
10
8
10
903

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents