Blocking And Tripping Logic For Evolving Power Swings - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
8.15.3.2
Transformer protection RET670 2.2 ANSI
Application manual
O/C EF protection to eliminate the initial fault and still make possible for the power
swing zones to operate for possible consecutive faults. A time delay between 150 and
300 ms is generally sufficient.

Blocking and tripping logic for evolving power swings

The second part of a complete Power swing logic (PSLPSCH) functionality is a
blocking and tripping logic for evolving power swings, see figure
The simplified logic is presented in figure 233. The logic controls the operation of the
underreaching distance protection zone (Zone 1) at power swings, caused by the faults
and their clearance on the adjacent power lines. The logic should generally be
configured between distance protection zones 1 and 2.
Configuration
The fault impedance should be detected within the external boundary of Power Swing
Detection (ZMRPSB, 68) function without power swing detected during the entire
fault duration. Configure for this reason the PUZMPSD to the functional output signal
of ZMRPSB (68) function, which indicates the measured impedance within its external
boundaries.
PUZMUR
AND
BLOCK
PUZMOR
PUZMPSD
PUPSD
ANSI06000237 V1 EN-US
Figure 233:
Blocking and tripping logic for evolving power swings
No system oscillation should be detected in power system. Configure for this reason
the PUPSD functional input to the PICKUP functional output of ZMRPSB (68)
function or to any binary input signal indicating the detected oscillations within the
power system.
0-tZL
0
0-tDZ
AND
OR
0
AND
-loop
Section 8
Impedance protection
230
and figure 231.
AND
BLKZMOR
AND
PUZMURPS
OR
AND
en06000237_ansi.vsd
SEMOD131360-55 v3