Figure 83:
Self-regulating effect of reactive power balance
Increase in power transfer
The increase in power transfer capability as a function of the degree of compensation
for a transmission line can be explained by studying the circuit shown in figure 84. The
power transfer on the transmission line is given by the equation 55:
( )
d
×
×
V
V
sin
=
=
A
B
P
-
X
X
Line
C
EQUATION1994-ANSI V1 EN-US
The compensation degree K
A
P
A
-jX
C
+jX
L
V
A
Q
A
ANSI06000590 V1 EN-US
Figure 84:
Transmission line with series capacitor
The effect on the power transfer when considering a constant angle difference (δ)
between the line ends is illustrated in figure 85. Practical compensation degree runs
500
1000
Transmission
500 kV
500 km
Line
Series
Compensation
k = 50 %
( )
d
×
×
V
V
sin
A
B
(
)
×
-
X
1 K
Line
C
is defined as equation
c
D
V
V
V
A
B
B
P
B
d
V
B
Q
B
en06000590_ansi.vsd
Section 8
Impedance protection
(S.C.)
Power flow
(MW)
1500
(T.L. + S.C.)
(T.L.)
en06000589.vsd
SEMOD168320-45 v2
(Equation 55)
209