Setting Guidelines - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
6.2.4
Transformer protection RET670 2.2 ANSI
Application manual
is adapted according to the performance class (SvcClass) and reporting rate of the
connected instance of PHASORREPORT function block. On the other hand, when
3PHSUM uses external DFT reference, it also adapts its filtering according to the
SMAI reference block. Therefore, in order to avoid two different filtering applied to
the 3PHSUM block, both SMAI reference block and 3PHSUM shall be connected to
the same PHASORREPORT instance. In this example (Figure 47), SMAI3 adapts its
filtering according to PHASORREPORT1 instance 2 (due to connection) and
3PHSUM is adapting its filtering according to PHASORREPORT1 instance 1. On the
other hand, since 3PHSUM is set to receive external DFT reference from SMAI3,
therefore If settings for PHASORREPORT1 instances 1 and 2 above differ for
SvcClass or ReportRate, then 3PHSUM block will be affected by two different filtering
at the same time which is not possible. For example in Figure 47, PHASOR2 from
PHASORREPORT1 instance 1 may not be fully compliant with IEEE C37.118
standard.
Note: If the SMAI reference block is not connected to any PHASORREPORT block,
then 3PHSUM block can be freely connected to any PHASORREPORT block
regardless of its DFT reference setting.
Note: If more 3PHSUM blocks need to be used, all 3PHSUM blocks (using external
DFT ref) have to be connected to the same instance of PHASORREPORT blocks
(PHASOR1-32 of Instance number 1 or 2).
Note: If settings SvcClass and ReportRate are the same for different instances of
PHASORREPORT blocks, then 3PHSUM block can be freely connected to any of
them regardless of 3PHSUM block DFT reference setting or the reference SMAI block
connection.
Note: Violation of rules 2 or 3 results in non-compliancy with IEEE C37.118 standard
for some of the synchrophasors. In case of rule 2 violation, the non-compliancy only
applies to synchrophasors from instance 2 and the synchrophasors from instance 1 will
be still compliant. The non-compliancy with the standard may be quite obvious as in
case of rule 2 violation with different SvcClass settings. This produces big angle error.
On the other hand, it may be difficult to detect the non-compliancy with the standard if
rule 2 is violated with different ReportRates, or if rule 3 is violated. In such cases, the
synchrophasors may only fail to comply (with small error) in some particular test
case(s).
For more information regarding 3PHSUM block application, please refer to the
Application Manual under section Basic IED functions.

Setting guidelines

Based on the functionality and appearance in PCM600, the PMU reporting
functionality is categorized into 4 different categories (function block) as follows:
Wide area measurement system
GUID-83969957-DABF-4B9B-95C7-B9F0AF6E647A v2
Section 6
129

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents