Section 15
Control
698
principle for the use of QCBAY, LOCREM, LOCREMCTRL, SCILO,
SCSWI, SXCBR.
Figure
313
shows from which places the apparatus control function receives
commands. The commands to an apparatus can be initiated from the Control Centre
(CC), the station HMI or the local HMI on the IED front.
Station HMI
Local
HMI
IED
Apparatus
Apparatus
Control
CLOSE/OPEN
CLOSE/OPEN
breakers disconnectors grounding switches
ANSI08000227 V1 EN-US
Figure 313:
Overview of the apparatus control functions
Features in the apparatus control function:
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchronism check
Pole discrepancy supervision
Operation counter
Suppression of mid position
cc
GW
Local
HMI
IED
IED
Apparatus
Control
Control
CLOSE/OPEN
ANSI08000227.vsd
1MRK 504 163-UUS A
Station bus
Local
HMI
Transformer protection RET670 2.2 ANSI
Application manual