ABB RELION RET670 Applications Manual page 422

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

Section 8
Impedance protection
416
Voltage distribution on faulty lossless serial compensated line from fault point F to the
bus is linearly dependent on distance from the bus, if there is no capacitor included in
scheme (as shown in figure 204). Voltage V
drop D V
on the faulty line and lags the current I
L
The situation changes with series capacitor included in circuit between the IED point
and the fault position. The fault current I
capacitor, generally decreases total impedance between the sources and the fault. The
reactive voltage drop D V
Voltage drop DV
on series capacitor lags the fault current by 90 degrees. Note that
C
line impedance X
could be divided into two parts: one between the IED point and the
L1
capacitor and one between the capacitor and the fault position. The resulting voltage
V
in IED point is this way proportional to sum of voltage drops on partial
M
impedances between the IED point and the fault position F, as presented by
(
)
=
×
-
V
I
j X
X
M
F
L1
C
EQUATION1995-ANSI V1 EN-US
With bypassed
Source voltage
Source
X
S
~
I
F
ANSI06000605 V1 EN-US
Figure 203:
Voltage inversion on series compensated line
measured at the bus is equal to voltage
M
(see figure 204) is increased due to the series
F
on X
line impedance leads the current by 90 degrees.
L
L1
With inserted
capacitor
capacitor
V'
M
V
M
V
X
L1
X
F
X
C
21
en06000605_ansi.vsd
1MRK 504 163-UUS A
by 90 electrical degrees.
F
Pre -fault voltage
Fault voltage
Transformer protection RET670 2.2 ANSI
Application manual
(Equation 331)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents