Setting Of Reach In Resistive Direction - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
8.5.3.6
Transformer protection RET670 2.2 ANSI
Application manual
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
Z
0
m
= -
K
0 1
×
+
+
2
Z
1
Z
0
R
f
EQUATION1426 V1 EN-US
If the denominator in equation
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
×
X m
0
Re
( )
= -
Re
K
0
1
( )
2
+
Re
B
Im
EQUATION1427 V2 EN-US
( )
×
( )
X m
0
Im
=
Im
K
0
( )
2
+
Re
B
Im
EQUATION1428 V2 EN-US
Parallel line is out of service and grounded in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
2
æ
X
m0
×
ç
------------------------- -
R
=
R
1
+
0E
0
2
è
R
+
X
0
0
EQUATION561 V1 EN-US
2
æ
X
m0
×
------------------------- -
X
=
X
ç
1
0E
0
2
è
R
+
X
0
0
EQUATION562 V1 EN-US

Setting of reach in resistive direction

Set the resistive reach independently for each zone, for phase-to-ground loop (RIPE)
measurement.
180
is called B and Z0m is simplified to X0m, then the
B
( )
2
B
B
( )
2
B
ö
÷
2
ø
ö
÷
2
ø
Section 8
Impedance protection
(Equation 180)
(Equation 181)
(Equation 182)
SEMOD154704-69 v3
(Equation 183)
(Equation 184)
SEMOD154704-76 v1
309