Interlocking For Busbar Grounding Switch Bb_Es (3) - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

Section 15
Control
15.3.7
15.3.7.1
744
Section 1
(WA1)A1
(WA2)B1
BH_LINE
BH_LINE
ANSI04000503 V1 EN-US
Figure 350:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic is the same as for the logic for the double-breaker
configuration.
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from breaker and a half (BH) that contains the above
information.

Interlocking for busbar grounding switch BB_ES (3)

Application
The interlocking for busbar grounding switch (BB_ES, 3) function is used for one
busbar grounding switch on any busbar parts according to figure 351.
89G
en04000504.vsd
ANSI04000504 V1 EN-US
Figure 351:
Switchyard layout BB_ES (3)
The signals from other bays connected to the module BB_ES are described below.
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BH_LINE
BH_LINE
en04000503_ansi.vsd
1MRK 504 163-UUS A
A2
B2
Transformer protection RET670 2.2 ANSI
Application manual
IP14164-1 v4
M15015-3 v7
M15053-4 v4