Event Function Event - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

Section 18
Monitoring
18.5
18.5.1
18.5.2
884
SpChAlmTime: Time delay for spring charging time alarm.
tDGasPresAlm: Time delay for gas pressure alarm.
tDGasPresLO: Time delay for gas pressure lockout.
DirCoef: Directional coefficient for circuit breaker life calculation.
RatedOperCurr: Rated operating current of the circuit breaker.
RatedFltCurr: Rated fault current of the circuit breaker.
OperNoRated: Number of operations possible at rated current.
OperNoFault: Number of operations possible at rated fault current.
CBLifeAlmLevel: Alarm level for circuit breaker remaining life.
AccSelCal: Selection between the method of calculation of accumulated energy.
OperTimeDelay: Time delay between change of status of trip output and start of main
contact separation.

Event function EVENT

Identification
Function description
Event function
Application
When using a Substation Automation system with LON or SPA communication, time-
tagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT). The EVENT function block is used for remote
communication.
Analog, integer and double indication values are also transferred through the EVENT
function.
IEC 61850
IEC 60617
identification
identification
EVENT
S00946 V1 EN-US
Transformer protection RET670 2.2 ANSI
1MRK 504 163-UUS A
IP14590-1 v2
SEMOD167950-2 v2
ANSI/IEEE C37.2
device number
-
M12805-6 v11
Application manual