The load impedance [Ω/phase] is a function of the minimum operation voltage and the
maximum load current:
V
=
min
Z
load
×
3
I
max
EQUATION1781-ANSI V1 EN-US
Minimum voltage V
and maximum current Imax are related to the same operating
min
conditions. Minimum load impedance occurs normally under emergency conditions.
Because a safety margin is required to avoid load encroachment under
three-phase conditions and to guarantee correct healthy phase IED
operation under combined heavy three-phase load and ground faults,
consider both: phase-to-phase and phase-to-ground fault operating
characteristics.
To avoid load encroachment for the phase-to-ground measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the minimum
load impedance.
RFPEZx
0.8
Z
load
EQUATION792 V2 EN-US
This equation is applicable only when the loop characteristic angle for the single
phase-to-ground faults is more than three times as large as the maximum expected
load-impedance angle. More accurate calculations are necessary according to the
equation below:
RFPEZx
0.8
Z
cos
load
min
EQUATION578 V5 EN-US
Where:
ϑ
is a maximum load-impedance angle, related to the minimum load impedance conditions.
All this is applicable for all measuring zones when no power swing detection element
is in the protection scheme. Use an additional safety margin of approximately 20% in
cases when a power swing detection element is in the protection scheme, refer to the
description of the power swing detection (ZMRPSB, 78) function.
2
R Zx R Zx
1
0
sin
2
X Zx
1
X Zx
0
Section 8
Impedance protection
(Equation 189)
(Equation 190)
(Equation 191)
311