Section 9
Current protection
582
Mode
Set value
BC
CA
A
B
C
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is smaller than the set pick up power value Power1(2)
Formula used for complex power calculation
*
*
=
×
-
S
V
(
I
I
)
BC
B
C
EQUATION2059-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
CA
C
A
EQUATION2060-ANSI V1 EN-US
*
= ×
×
S
3
V
I
A
A
EQUATION2061-ANSI V1 EN-US
*
= ×
×
S
3
V
I
B
B
EQUATION2062-ANSI V1 EN-US
*
= ×
×
S
3
V
I
C
C
EQUATION2063-ANSI V1 EN-US
Transformer protection RET670 2.2 ANSI
1MRK 504 163-UUS A
(Equation 457)
(Equation 458)
(Equation 459)
(Equation 460)
(Equation 461)
Application manual