Control Units
6.2 Control Unit CU310 DP (PROFIBUS)
Note
A teleservice adapter can be connected to the PROFIBUS interface (X21) for remote
diagnosis purposes.
The power supply for the teleservice terminals 2 and 7 withstands a max. load and continued
short-circuit current of 150 mA.
PROFIBUS connector
At the first and last node (device) in a line, the terminating resistors must be switched-in in
order to ensure disturbance/noise-free communications.
The terminating resistors are activated in the connector.
The cable shield must be connected at both ends over large-surface area contacts.
6.2.3.8

X23 HTL/ TTL encoder interface

Table 6-7
Encoder connection X23
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Type: 15-pin SUB D connector
6-12
Signal name
Reserved, do not use
SSI_CLK
SSI_XCLK
PENC
PENC
PSENSE
M
Reserved, do not use
MSENSE
RP
RN
BN
BP
AN_SSI_XDAT
AP_SSI_DAT
Technical specifications
SSI clock, positive
SSI clock, negative
Encoder power supply
Encoder power supply
Remote sense encoder power supply (P)
Electronic ground
Remote sense encoder power supply (N)
R track positive
R track negative
B track negative
B track positive
A track negative / SSI data negative
A track positive / SSI data positive
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0