9.5 Information about Electromagnetic Compatibility (EMC) and Cable Routing
Avoid, where possible, routing unshielded cables, connected to the drive line-up, in the
immediate vicinity of noise sources, e.g. transformers. Signal lines (shielded and unshielded)
connected to the drive line-up, must be routed as far as possible away from strong external
magnetic fields (e.g. transformers, line reactors). In both cases, a distance of ≥ 300 mm is
usually sufficient.
Signal and DC power supply cables
Operating unshielded signal and direct current supply cables (e.g. 24 V infeed with external
supply):
• Direct current supply cables: Max. permissible length: 10 m
• Unshielded signal cables: Max. permissible length: 30 m (without additional wiring)
For greater lengths, suitable wiring must be connected by the user to provide overvoltage
protection. For example:
Table 9-5
DC supply
Weidmüller
Type no.: PU DS 24V 16A
Weidmüller GmbH & Co. KG
An der Talle 89
33102 Paderborn
Tel. 05252/960-0
Fax 05252/960-116
www.weidmueller.com
Caution
The connected signal and power cables must not cover the ventilation slots.
Caution
Unshielded signal cables must not be routed parallel to power cables.
9-14
Recommendations for overvoltage protection
24 V signal cables
Weidmüller
Type no.: MCZ OVP TAZ
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
Equipment Manual AC Drive