Supplementary system components and encoder system integration
7.3 Sensor Module Cabinet 10 (SMC10)
7.3.2

Safety information

Caution
The cooling clearances of 50 mm above and below the components must be observed.
Notice
Only one measuring system can be connected to each Sensor Module.
Note
There may be no electrical connection between the measuring system housing and the
measuring system electronics (this requirement is fulfilled for most encoder systems). If this
is not carefully observed, then under certain circumstances the system will not be able to
reach the required noise immunity (there is then a danger of equalization currents flowing
through the electronics ground).
Caution
Connecting cables to temperature sensors must always be installed with shielding. The
cable shield must be connected to the chassis potential at both ends over a large surface
area. Temperature sensor cables that are routed together with the motor cable must be
twisted in pairs and shielded separately.
7-22
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0