Siemens SINAMICS S120 Equipment Manual page 297

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Figure 9-2
1. Line supply input
2. Motor cable
3. Rear metal panel
4. Use suitable clamps/clips to reliably connect the shield of the motor and field cable to the
5. Shielded cable
Alternatively, the cable shields can be connected to them metal mounting plate using pipe
clamps and serrated rails. The cable length between the shield contact point and the
terminals for cable conductors must be kept as short as possible.
Shield connection plates with pre-prepared clip contacts are available for connecting the
shields for power cables of Power Modules.
All cables inside the cabinet must be connected as closely as possible to parts connected
with cabinet ground, such as a mounting plate or cabinet wall. Ducts made of sheet steel or
routing cables between between steel sheets (e.g. between the mounting plate and back
wall) should provide adequate shielding.
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
9.5 Information about Electromagnetic Compatibility (EMC) and Cable Routing
Shielding of a Power Module PM340
rear metal panel.
Cabinet design and EMC for components, Blocksize format
9-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents