Information On Cabinet Cooling; General - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

9.7

Information on cabinet cooling

9.7
9.7.1

General

Electrical cabinets can be cooled, using among other things the following:
• filtered fans
• heat exchangers or
• cooling units.
The decision in favor of one of these methods will depend on the prevailing ambient
conditions and the cooling power required.
The air routing within the electrical cabinet and the cooling clearances specified here must
be observed. No other components or cables must be located in these areas.
Caution
If you do not observe the guidelines for installing SINAMICS equipment in the cabinet, this
can reduce the service life of the equipment and result in premature component failure.
You must take into account the following specifications when mounting/installing SINAMICS
components:
• Cooling clearance
• Cable routing
• Air guidance, air-conditioner
Table 9-7
Cooling clearances around the components
Component
CU310 DP
CU310 PN
CUA31
SMCxx
Line filters
Line reactors
PM340, Blocksize, frame size A
PM340, Blocksize, frame size B
PM340, Blocksize, frame size C
PM340 Blocksize, frame sizes D and E
PM340, Blocksize, frame size F
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
Cabinet design and EMC for components, Blocksize format
Clearance above and below
in mm and (inches)
50 (1.97)
50 (1.97)
50 (1.97)
50 (1.97)
100 (3.93)
100 (3.93)
100 (3.93)
100 (3.93)
125 (4.92)
300 (11.81)
350 (13.77)
9.7 Information on cabinet cooling
Lateral clearance
in mm and (inches)
0
0
0
0
0
30 (1.18)
40 (1.57)
50 (1.97)
0
0
9-17