7.2.3.5

Digital inputs X520

Table 7-8
Screw terminal X520
Terminal
1
2
3
4
5
6
Max. cross-section that can be connected: 1.5 mm²
Type: Screw terminal 1 (see Appendix A)
1) DI: digital input; M: electronic ground M1: Ground reference
Note
To enable the digital inputs to function, terminal M1 must be connected. This can be done as
follows:
1) Connect the reference ground of the digital inputs, or
2) a jumper to terminal M
(Notice: this removes isolation for these digital inputs).
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
Supplementary system components and encoder system integration
Designation
1)
DI 0
DI 1
DI 2
DI 3
M1
M
7.2 Terminal Module 31 (TM31)
Technical specifications
Voltage: - 3 V to +30 V
Typical current consumption: 10 mA at 24 V DC
Isolation: The reference potential
is terminal M1
Signal propagation times:
L → H approx. 50 μs
H → L: approx. 100 µs
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
7-9