Cabinet design and EMC for components, Blocksize format
9.5 Information about Electromagnetic Compatibility (EMC) and Cable Routing
9.5.2

Cable Shielding and Routing

In order to comply with the EMC requirements, certain cables must be routed apart from
other cables and from certain components. To full EMC requirements, the following cables
must be used with shields:
• Power supply cables from line filter via line reactor to Power Module
• All motor cables (if necessary, including cables for motor holding brake)
• Cables for "fast inputs" of the Control Unit
• Cables for analog direct voltage/current signals
• Signal cables for sensors
• Cables for temperature sensors
Alternative measures (e.g. routing behind mounting plates, suitable clearances) can also be
used provided they have similar results. This excludes measures that relate to the design,
installation, and routing of motor power cables and signal cables. If unshielded cables are
used between the line connection point and line filter, make sure that no interfering cables
are routed in parallel.
The cable shields must be connected as close to the conductor terminal connections as
possible to ensure a low-impedance connection with cabinet ground.
9-12
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0