Supplementary system components and encoder system integration
7.2 Terminal Module 31 (TM31)
7.2.3.8

Analog inputs X521

Table 7-11
Terminal block X521
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 1.5 mm²
Type: Screw terminal 1 (refer to Appendix A)
1) AI: analog inputs; P10/N10: auxiliary voltage; M or GND: ground reference
Caution
If more than 40 mA flows through the analog current input, then the component could be
destroyed.
The common mode range may not be violated. This means that the analog differential
voltage signals can have a maximum offset voltage of +/-30 V DC with respect to the ground
potential. If the range is infringed, incorrect results may occur during analog/digital
conversion.
7.2.3.9

S5 current/voltage changeover switch for analog inputs

Table 7-12
Current/voltage selector S5
7-12
Name
1)
AI 0+
AI 0-
AI 1+
AI 1-
P10
M
N10
M
Switch
S5.0
S5.1
Technical specifications
You can set the following input signals using the
appropriate parameters:
Voltage: -10 V to 10 V; R
Current 1: 4 mA to 20 mA; R
Current 2: -20 mA to 20 mA; R
Current 3: 0 mA to 20 mA; R
Resolution: 12 bits
Auxiliary voltage:
P10 = 10 V
N10 = -10 V
Continued-short-circuit-proof
Function
Selector voltage (V)/current (I) Al0
Selector voltage (V)/current (I) Al1
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
= 100 kΩ
i
= 250 Ω
i
= 250 Ω
i
= 250 Ω
i
Equipment Manual AC Drive