Power Modules
3.1 Power Modules Blocksize (PM340)
Table 3-8
For frame sizes D to F, the terminals are accessed by releasing the tongue at the side of the
terminal covers using a suitable flat screwdriver. The cover can then be pushed upwards and
engaged in this position as shown in the following diagram.
3-28
PM340, load terminals - tightening torques
Frame size
A
B
C
D
E
F
Tightening torques
Nm
Nm
Nm
Nm
Nm
Nm
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
1.1
1.5
2.25
6
6
13