8.8.7

Analog output range

This parameter is used to define the output current range.
Function code
0
1 (default)
8.8.8

Analog output source

The analog output can be used for a range of purposes. This parameter defines the tag that
controls the analog output.
Function code
0
1 (default)
2
3
4
5
8.8.9

Response of analog output to faults or SIMATIC STOP

This parameter defines the response of the analog output following a fault of the SIWAREX
module or SIMATIC STOP.
Function code
0 (default)
1
2
3
8.8.10

Start value for the analog output

This parameter defines the start value of the scaling of the analog output and thus
corresponds to 0 mA or 4 mA, depending on the setting. The value can be greater or less
than the end value.
8.8.11

End value for the analog output

This parameter defines the end value of the scaling of the analog output and thus
corresponds to 20 mA.
SIWAREX WP251
Manual, 12/2015, A5E37203357A
Basis for the analog output
Gross weight (rounded according to DR 3)
Net weight (rounded according to DR 3)
Tare weight (rounded according to DR 3)
Coarse/fine signal (specified percentage from DR 25)
Control using data record DR 17
Control using S7-I/O ("s_I_O_DATA.AQ_CONTROL")
Response
Switch off
Retain function
Output configured substitute value (e.g. 3.5 mA)
Output maximum value (24 mA)
Scale parameters and functions
8.8 DR 7 Process interfaces
Output current
0 ... 20 mA
4 ... 20 mA
93