KEB COMBIVERT F4-C Applications Manual page 83

Hide thumbs Also See for COMBIVERT F4-C:
Table of Contents

Advertisement

Operating and Appliance Displays
ru.24 Display OL - counter
Adr.
2018h
To prevent „E.OL" errors caused by too high loads (load reduction), the internal counter content of the OL-counter can
be made visible. At 100 % the inverter switches off with the error „E.OL". The error can be reset only after a cooling time
(blinking display „E.nOL").
ru.29 Heat sink temperature
Adr.
201Dh
ru.29 displays the current heat sink temperature of the inverter. Below 20°C noF (no Function) is displayed.
ru.30 Display PI-controller output
Adr.
201Eh
A universal PI-controller is integrated into the inverter. It can be used externally as well as internally. So that the
controller is independent as much as possible, the indicated manipulated variable is given out in percentage in relation
to a +/- 10V signal.
ru.31 Operating hours-meter 1
Adr.
201Fh
The operating hours-meter 1 displays the time the inverter has been switched on. The indicated value includes all
operating phases. On attaining the maximum value (approx. 7.5 years) the display remains on the maximum value.
ru.32 Operating hours-meter 2
Adr.
2020h
The operating hours-meter 2 displays the time the inverter has been active (motor controlled). On attaining the maximum
value (approx. 7.5 years) the display remains on the maximum value.
©
KEB Antriebstechnik, 1999
All Rights reserved
min
max
0
100
min
max
0
100
min
max
-100
100
min
max
0
65535
min
max
0
65535
Name: Basis
KEB COMBIVERT F4-C
Functional Description
%
1
°C
1
%
0,1
h
1
h
1
Date
09.04.99
ANTRIEBSTECHNIK
default
-
default
-
default
-
default
-
default
-
Chapter
Section
Page
13
6
1