Functional Description
ru.11 DC-link voltage
Adr.
200Bh
Display of actual DC-link voltage. Typical values are for
normal operation: 230V-class approx. 300-330V
400V-class approx. 530-620V
ru.12 DC-link voltage peak value
Adr.
200Ch
ru.12 allows the detection of short-time voltage rises within an operating cycle. For that the highest detected value of
ru.11 is stored in ru.12. The peak value memory is cleared by pressing the keys UP or DOWN or by bus by writing any
chosen value to the address of ru.12. The disconnection of the inverter also results in a clearing of the memory.
ru.13 Output voltage
Adr.
200Dh
Display of actual output voltage
ru.14 Input terminal status
Adr.
200Eh
Display of the actual triggered digital inputs. Whether the input is inverted or the internal acceptance takes place
through edge triggering or strobe is irrelevant for the display. According to following table a certain decimal value is
given out for each digital input. If several inputs are triggered then the sum of their decimal values is displayed.
Bit -No.
Chapter
Section
Page
6
1
10
min
max
200
999
min
max
200
999
min
max
0
999
min
max
0
255
Decimal value
0
1
1
2
2
4
3
8
4
16
5
32
6
64
7
128
Date
Name: Basis
09.04.99
KEB COMBIVERT F4-C
Operating and Appliance Displays
V
1
in case of fault (E.OP):
%
1
V
1
-
1
Input
ST (control release)
RST (Reset)
F (rotation forward)
R (rotation reverse)
I1 (prog. input 1)
I2 (prog. input 2)
I3 (prog. input 3)
I4 (prog. input 4)
default
-
230V-class approx.390V
400V-class approx.800V
default
-
default
-
default
-
Terminal
19
20
10
11
4
5
6
7
©