Operation
DC-braking
DC-braking time
Section
Page
Chapter
4
3
10
At DC-braking the motor is not decelerated by the ramp. The fast stopping is done by
a dc-voltage that is given onto the motor winding. This parameter defines how DC-
braking is triggered.
Value
Activation
0
DC-braking switched off
1
DC-braking at taking away direction of rotation and attaining 0 Hz. Braking
time depends on CP.21 or until the next rotation setting.
2
DC-braking as soon as rotation setting is missing. Braking time depends on
the actual frequency.
3
DC-braking as soon as the direction of rotation changes. Braking time
depends on the actual frequency.
4
DC-braking at taking away direction of rotation and when actual frequency
falls below 4 Hz.
5
DC-braking if actual frequency falls below 4 Hz.
6
DC-braking as soon as setpoint value falls below 4 Hz.
7
DC-braking, if input I3 (terminal X1.6) is switched. Braking time depends on
the actual frequency.
8
DC-braking for as long as input I3 (terminal X1.6) is activated.
9
DC-braking after switching on the modulation. Braking time depends on
CP .21.
Factory setting:
Remarks:
Customer setting:
The braking time is evaluated in dependence on CP.20:
- entered time = braking time
- entered time refers to 100 Hz and is reduced/increased in proportion to the
actual frequency
Setting range:
Resolution:
Factory setting:
Customer setting:
Calculation of braking time:
t
B
ist
Date
Name: Basis
KEB COMBIVERT F4-C
20.03.98
Enter-Parameter
_______
0,00...100 s
0,05 s
10 s
_______
CP.21 * f
ist
=
100 Hz
CP - Parameter
7
f
100 Hz
f
ist
t
CP.21
B ist
©
KEB Antriebstechnik, 1997
All Rights reserved
t