Loading Setpoints From A File; Quick Setup - GE 845 Instruction Manual

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

CHAPTER 3: INTERFACES
Loading Setpoints
from a File
CAUTION:

Quick Setup

845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
An error message occurs when attempting to upload a setpoint file with a revision
number that does not match the relay firmware. If the firmware has been upgraded
since saving the setpoint file, see Upgrading Setpoints Files to a New Revision for
instructions on changing the revision number of a setpoint file.
The following procedure illustrates how to load setpoints from a file. Before loading a
setpoints file, it must first be added to the 845 environment as described in the section,
Adding Setpoints Files to the Environment.
1.
Select the previously saved setpoints file from the File pane of the 845 software main
window.
2.
Select the Offline > Edit Settings File Properties menu item and verify that the
corresponding file is fully compatible with the hardware and firmware version of the
target relay. If the versions are not identical, see Upgrading Setpoint Files to a New
Revision for details on changing the setpoints file version.
3.
Right-click on the selected file and select the Write Settings File to Device item.
4.
Select the target relay from the list of devices shown and click Send. If there is an
incompatibility, an error of the following type occurs:
If there are no incompatibilities between the target device and the settings file, the data is
transferred to the relay. An indication of the percentage completed is shown in the bottom
of the main window.
The Quick Setup item is accessed from the EnerVista software from different screens.
Online and offline settings changes are made from the corresponding Quick Setup screen.
SOFTWARE INTERFACE