GE 845 Instruction Manual page 440

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

FLEXLOGIC
4–336
damage the equipment. A FlexElement can be used for simple detection of V/Hz values,
and to issue an Alarm, or Trip, if detected above Pickup setting. Since the base unit for V/Hz
= 1.00, programming of the pickup setpoint is straight forward for the desired FlexElement
operation. For the example given here, a value of 1.200 pu has been selected.
Input 1(+): Volts Per Hertz 1Input 2(-): OffOperating Mode: AbsoluteInput Comparison
Mode: LevelDirection: OverPickup: 1.200 puHysteresis: 8.3 %
Now, if the FlexElement is needed to drop down when the V/Hz ratio becomes equal to 1.1,
the hysteresis can be calculated as:1.2pu-1.1pu = 0.1 puHysteresis = (0.1*100)/1.2 = 8.3%
RTD inputs for Top-Bottom oil temperature on Transformer
The difference between the Top-oil and the Bottom-oil temperatures of a transformer tank
can be monitored, and if this difference exceeds a specified level, can be an indication of a
problem associated with oil pumps forcing the circulation of the oil, or problems
associated with the transformer cooling equipment. A FlexElement can be programmed to
detect the Top-Bottom oil difference, and issue an alarm, trip, or energize a contact used
for switching-in/out transformer equipment. The setpoints of the FlexElement below reflect
detecting a 5°C degree temperature difference between the istalled RTDs measuring the
top and bottom oil temperatures:
Input 1(+): RTD 1 (top-oil)
Input 2(-): RTD 2 (bottom-oil)
Operating Mode: Absolute
Input Comparison Mode: Level
Direction: Over
Pickup: 0.050 pu
Hysteresis:
60.0%
With an RTD
= 100°C, the required temperature difference of 5°C, would be computed
BASE
as a pickup value of 5°C/100°C = 0.050 pu.
If it is required to drop out the operation of the FlexElement when the temperature
difference becomes 2°C, the hysteresis would be calculated as 5°C/100°C - 2°C/100°C =
3°C/100°C = 0.03 pu. Therefore:
Hysteresis = (0.03 pu *100)/0.05 = 60%
High Breaker Arcing current detection
High breaker arcing current can be detected by using a FlexElement during the opening of
a breaker. One or more FlexElements can be configured for detecting levels of maximum
arcing current during the tripping of a particular breaker, and give an indication for the
health of the breaker.
The base unit for the breaker arcing current is programmed in the relay as: BASE = 2000
2
kA
*cycle
Input 1(+): Total Arcing Current
Input 2(-): Off
Operating Mode: Absolute
Input Comparison Mode: Level
Direction: Over
Pickup: 2.500 pu
Hysteresis: 0.0 %
To configure the pickup setpoint for a total arcing current of 5000kA
pickup value can be calculated as follows:
2
Pickup = 5000kA
*cycle/2000 kA
2
*cycle = 2.500 pu
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS
2
/cycle, the per-unit