Timers - GE 845 Instruction Manual

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

CHAPTER 4: SETPOINTS

Timers

845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
FlexLogic™ provides latches which by definition have a memory action, remaining in the
set state after the set input has been asserted. However, they are volatile; that is, they reset
on the re-application of control power.
When making changes to settings, all FlexLogic™ equations are re-compiled whenever
any new setting value is entered, so all latches are automatically reset. If it is necessary to
re-initialize FlexLogic™ during testing, for example, it is suggested to power the unit down
then back up.
Path:
Setpoints > FlexLogic > Timers
There are 32 identical FlexLogic timers available. These timers can be used as operators for
FlexLogic equations.
TIMER 1 TYPE
Range: Milliseconds, Seconds, Minutes
Default: Milliseconds
The setpoint is used to select the time measuring unit.
TIMER 1 PICKUP DELAY
Range: 0 to 60000 s in steps of 1 s
Default: 0 s
The setpoint sets the time delay to Pickup. If a Pickup delay is not required, set this
function to "0".
FLEXLOGIC
4–327

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents