CHAPTER 4: SETPOINTS
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Parameters for Goose TX
GOOSE ID: The range of the setting is 129-characters
Time to live (ms): The range of the setting is 1000 to 60000 in steps of 1000
Multicast MAC: The standard MAC address limit. Make sure to configure the MAC with
the least significant bit in the most significant byte, set to 1.
Example:
01: 0C: CD: 00: 00: 04
VLAN priority: The range of the setting is 0 to 7 in steps of 1
VLAN identifier: The range of the setting is 0 to 4095 in steps of 1
Goose Transmission Dataset Items
The following provides details for working with dataset items.
Change the Order of Configured Dataset Items
1.
Select the row in which the order is to be changed.
2.
Use the "up" arrow if you want to shift the row to the top. Use the "down" arrow to shift
the row down.
Figure 4-27: Re-order DataSet Items
Delete a Dataset Item
The following list gives the two methods that can be used to delete a dataset item.
Select the row in which the dataset item is to be deleted and click the "x" button.
Figure 4-28: Delete a Dataset Item
Select the row in which the dataset item is to be deleted then right click and select the
displayed "Delete FCDA" option.
Figure 4-29: Delete FCDA Option
Number of DAs
Depending on the configured dataset items, the "Number of DAs" counter increases
automatically.